A oil stain around the suction valve of this screw compresso, evidence of a refrigerant leak
|
An oil stained air cooled condenser, a sure sign of a tube or tubes leaking refrigerant
|
A poorly maintained electrical control panel, not by Coolmation!
|
Badly brazed joint around a high pressure switch leaking oil & refrigerant
|
A heavily clogged air cooled condenser which can increase running costs by 30%. A foam cleaning agent is required to loosen the baked in dirt
|